Welcome to the report of the PQopen measurement network for 2026-10.

Summary

Evaluated is the 1s-mean value of the mains frequency measured in CH/Solothurn.

StatisticsValue and occurrence
MIN49.8742 Hz (2026-10-09 22:00:50 CEST)
1% Percentile49.9435 Hz
MEAN49.9994 Hz
99% Percentile50.0512 Hz
MAX50.1069 Hz (2026-10-05 16:02:23 CEST)

Daily Mean

Rate of Change of Frequency (ROCOF)

Frequency Spread

Oscillations (2-5 Hz)

Oscillations can be detected (as reported in the past) mainly in the Netherlands as well as northern Germany and Denmark. The following graphs visualize the timeseries of Bandpass-filtered Oscillations in the range of 2-5 Hz, which are dominant in these areas.

Interestingly, the Oscillation forced by the wind power generators are much more modulating in comparison to the Oscillations in NL, which are forced by PV infeed.

Other Abnormalities

Deviations of frequency below and above the ±100 mHz band, with the change to the previous month in brackets:

< 49.9 Hz> 50.1 Hz
Count of threshold crossings51 (+27)2 (-22)
Number of seconds below/above686 (+465)28 (-421)

Events

Timestamp (UTC)Timestamp (CET)TextCategory
2026-10-31 09:34:372026-10-31 10:34:37DE: Neurath F (1053 MW)Generation Outage
2026-10-30 13:50:032026-10-30 14:50:03TR: Voltage Dip with loss of loadLoss of load
2026-10-30 12:30:382026-10-30 13:30:38SE4<>LT: Klapeida-Nybro (NordBalt) 700 MWTransmission Outage
2026-10-26 23:44:402026-10-27 00:44:40FR: CATTENOM 2 (1300 MW)Generation Outage
2026-10-26 09:55:242026-10-26 10:55:24DE/BerlinLocal Power Outage
2026-10-24 06:05:412026-10-24 08:05:41FR: BLAYAIS 2 (910 MW)Generation Outage
2026-10-21 07:39:142026-10-21 09:39:14Spain: Unknown Generation OutageGeneration Outage
2026-10-13 23:04:382026-10-14 01:04:38FR: GOLFECH 2 (1310 MW)Generation Outage
2026-10-07 09:31:262026-10-07 11:31:26SE: Unknown reason yetGeneration Outage
2026-10-06 21:44:462026-10-06 23:44:46ES: COFRENTES (1064 MW)Generation Outage
2026-10-06 08:15:002026-10-06 10:15:00SE: Unknown fast drop of Frequency in NordicTransmission Failure
2026-10-06 04:58:052026-10-06 06:58:05PL: Jaworzno 2 B7 (834 MW)Generation Outage
2026-10-04 17:18:242026-10-04 19:18:24DE<>SETransmission Failure
2026-10-01 05:11:062026-10-01 07:11:06High Amplitude Inter-Area Oscillation (0.37 Hz)Frequency Swing

Central Europe Area

Nordic Area

CE & Nordic Area

Yours,
Michael