Welcome to the report of the PQopen measurement network for 2026-08.

News of PQopen Network

New Location in Baltic: LV/Riga. This very interesting measurement point makes the dynamics visible in combination with power exchange with Nordic area.

Summary

Evaluated is the 1s-mean value of the mains frequency measured in CH/Solothurn.

StatisticsValue and occurrence
MIN49.8868 Hz (2026-08-22 22:00:53 CEST)
1% Percentile49.9464 Hz
MEAN50.0002 Hz
99% Percentile50.0520 Hz
MAX50.1356 Hz (2026-08-23 16:16:52 CEST)

Daily Mean

Daily mean

Rate of Change of Frequency (ROCOF)

ROCOF

Frequency Spread

Frequency spread

Other Abnormalities

Deviations of frequency below and above the ±100 mHz band, with the change to the previous month in brackets:

< 49.9 Hz> 50.1 Hz
Count of threshold crossings10 (+3)28 (+10)
Number of seconds below/above131 (+83)484 (+370)

Events

List of all detected events
Timestamp (UTC)Timestamp (CET)TextCategory
2026-08-29 16:57:192026-08-29 18:57:19NL: TTB-TTG/380/DIELE-MEEDEN/WSTransmission Failure
2026-08-26 08:28:142026-08-26 10:28:14NO: SIMA G1 HYDRO (315 MW)Generation Outage
2026-08-26 04:31:512026-08-26 06:31:51NO: SIMA G1 HYDRO (315 MW)Generation Outage
2026-08-25 20:28:422026-08-25 22:28:42NO: SIMA G1 HYDRO (315 MW)Generation Outage
2026-08-25 07:08:502026-08-25 09:08:50NO: SIMA G1 HYDRO (315MW)Generation Outage
2026-08-24 15:49:132026-08-24 17:49:13France: GOLFECH 2 (1310MW)Generation Outage
2026-08-22 18:18:592026-08-22 20:18:59LV: start of series of multiple voltage dipsVoltage Dip
2026-08-21 09:13:122026-08-21 11:13:12Eastern GermanyFrequency Swing
2026-08-20 12:17:092026-08-20 14:17:09Southern-East EuropeFrequency Swing
2026-08-19 10:17:112026-08-19 12:17:11IFA-2: Tourbe-Dædalus (1014 MW)Transmission Outage
2026-08-19 02:57:462026-08-19 04:57:46Estlink?Transmission Failure
2026-08-18 12:43:072026-08-18 14:43:07Estlink?Transmission Failure
2026-08-18 12:38:542026-08-18 14:38:54Southern-East EuropeGeneration Outage
2026-08-18 06:33:342026-08-18 08:33:34France: TRICASTIN 3 (915 MW)Generation Outage
2026-08-17 12:20:392026-08-17 14:20:39Southern-East EuropeFrequency Swing
2026-08-16 06:10:002026-08-16 08:10:00France: PALUEL 4 (1330 MW)Generation Outage
2026-08-15 03:30:022026-08-15 05:30:02Failure in Northern Germany, possible trip of transmission lineFrequency Swing
2026-08-14 19:17:442026-08-14 21:17:44SpainVoltage Dip
2026-08-13 13:35:592026-08-13 15:35:59Southern-East EuropeFrequency Swing
2026-08-13 06:00:242026-08-13 08:00:24France: CRUAS 2 (915MW)Generation Outage
2026-08-11 22:01:472026-08-12 00:01:47TR/Istanbul: UPS OperationLocal Power Outage
2026-08-11 04:20:072026-08-11 06:20:07PL: Opole B6 (833MW)Generation Outage
2026-08-09 19:17:202026-08-09 21:17:20TR/Istanbul: UPS OperationLocal Power Outage
2026-08-08 14:56:382026-08-08 16:56:38NL: Onyx Power 731MW in RotterdamGeneration Outage
2026-08-08 14:06:232026-08-08 16:06:23Southern-East EuropeFrequency Swing
2026-08-07 01:56:492026-08-07 03:56:49Northern Germany; Transmission Failure between Nordic and CEFrequency Swing
2026-08-04 10:39:492026-08-04 12:39:49Southern-East EuropeFrequency Swing
2026-08-03 13:24:292026-08-03 15:24:29Disconnection of Offshore Windpark?Frequency Swing
2026-08-02 12:01:452026-08-02 14:01:45NL/Amersfoort Oscillation Record: 250mHz p-p / 10V p-pOscillation
2026-08-02 07:49:242026-08-02 09:49:24Sourthern-East EuropeFrequency Swing
2026-08-01 21:40:302026-08-01 23:40:30Failure in Nordic/CE LinkTransmission Outage
2026-08-01 14:54:092026-08-01 16:54:09Spain (details unknown)Generation Outage

Event Metrics

Automatically derived from the event plots: frequency nadir/zenith (10-cycle moving average), peak ROCOF (500 ms window per ENTSO-E convention), settling time (time until every location stays within ±10 mHz of 50 Hz) and the location with the highest peak ROCOF.

Timestamp (UTC)EventMin in HzMax in HzPeak ROCOF in mHz/sSettling in sPeak location
2026-08-29 16:57:19NL: TTB-TTG/380/DIELE-MEEDEN/WS49.959050.0260371.87.9DE/Essen
2026-08-26 08:28:14NO: SIMA G1 HYDRO (315 MW)49.949250.040921.47.9FI/Helsinki
2026-08-26 04:31:51NO: SIMA G1 HYDRO (315 MW)49.931650.002436.87.9SE/Malmoe
2026-08-25 20:28:42NO: SIMA G1 HYDRO (315 MW)49.905549.999848.07.9SE/Malmoe
2026-08-25 07:08:50NO: SIMA G1 HYDRO (315MW)49.932950.030545.87.9SE/Malmoe
2026-08-24 15:49:13France: GOLFECH 2 (1310MW)49.935450.004998.97.9ES/Pamplona
2026-08-22 18:18:59LV: start of series of multiple voltage dips49.900750.09941015.27.9LV/Riga
2026-08-21 09:13:12Eastern Germany49.999950.0488132.27.9CH/Solothurn
2026-08-20 12:17:09Southern-East Europe49.943550.0723743.47.9ME/Podgorica
2026-08-19 10:17:11IFA-2: Tourbe-Dædalus (1014 MW)49.954350.013177.96.2AT/Graz
2026-08-19 02:57:46Estlink?49.963850.07101592.22.2FI/Helsinki
2026-08-18 12:43:07Estlink?49.972750.11281023.64.5FI/Helsinki
2026-08-18 12:38:54Southern-East Europe49.930749.997388.87.9AT/Graz
2026-08-18 06:33:34France: TRICASTIN 3 (915 MW)49.935149.980074.77.9ES/Pamplona
2026-08-17 12:20:39Southern-East Europe49.933549.991390.97.9ME/Podgorica
2026-08-16 06:10:00France: PALUEL 4 (1330 MW)49.954250.030441.67.9TR/Istanbul
2026-08-15 03:30:02Failure in Northern Germany, possible trip of transmission line49.906850.0427503.97.2DE/Stade
2026-08-14 19:17:44Spain50.001150.0455372.87.9ES/Pamplona
2026-08-13 13:35:59Southern-East Europe49.948550.0740979.47.9ME/Podgorica
2026-08-13 06:00:24France: CRUAS 2 (915MW)49.989450.042382.15.5DE/Essen
2026-08-11 22:01:47TR/Istanbul: UPS Operation0.000049.997825595.87.9TR/Istanbul
2026-08-11 04:20:07PL: Opole B6 (833MW)49.968850.015038.47.9ES/Pamplona
2026-08-09 19:17:20TR/Istanbul: UPS Operation49.976750.0567163.87.9TR/Istanbul
2026-08-08 14:56:38NL: Onyx Power 731MW in Rotterdam49.930949.995897.97.9ES/Pamplona
2026-08-08 14:06:23Southern-East Europe49.952850.07451136.87.9ME/Podgorica
2026-08-07 01:56:49Northern Germany; Transmission Failure between Nordic and CE49.883850.0653664.37.9DE/Stade
2026-08-04 10:39:49Southern-East Europe49.989950.021586.07.6AT/Graz
2026-08-03 13:24:29Disconnection of Offshore Windpark?49.851850.0819473.37.9DE/Stade
2026-08-02 12:01:45NL/Amersfoort Oscillation Record: 250mHz p-p / 10V p-p50.034750.0897214.57.9NL/Eindhoven
2026-08-02 07:49:24Sourthern-East Europe49.967650.000674.67.9ES/Pamplona
2026-08-01 21:40:30Failure in Nordic/CE Link50.008250.056757.07.9ES/Pamplona
2026-08-01 14:54:09Spain (details unknown)49.952250.0160458.67.9ES/Pamplona

Below, there are several graphs, each representing a detailed time series plot of cycle-by-cycle frequency as well as 10-cycle moving average, phase angle difference and voltage magnitude.

Central Europe Area

France: TRICASTIN 3 (915 MW)
2026-08-18 06:33:34 (UTC): Generation Outage France: TRICASTIN 3 (915 MW)

France: GOLFECH 2 (1310MW)
2026-08-24 15:49:13 (UTC): Generation Outage France: GOLFECH 2 (1310MW)

Nordic Area

CE & Nordic Area


Yours,
Michael